Product Model & Spec. Parameter Item |
GN30-12/400-12.5 | GN30-12/630-20 | GN30-12/1000- 31.5 | GN30-12/1250- 31.5 | |
GN30- 12D/400-12.5 |
GN30-12D/630-20 | GN30- 12D/1000-31.5 |
GN30- 12D/1250-31.5 |
||
Rated voltage (kV) | 12 | ||||
Rated current (A) | 400 | 630 | 1000 | 1250 | |
4S rated short-time withstand current (kA) |
12.5 | 20 | 31.5 | ||
Rated peak withstand current (kV) | 31.5 | 50 | 80 | ||
Rated insulation level |
Power frequency withstand voltage for 1 minute (kV) |
Phase-phase voltage, voltage to ground:42; Break voltage:48 | |||
Lighting impulse voltage (kV) | Phase-phase voltage, voltage to ground:75; Break voltage:85 |
Phase sapcing p Dimensions Model |
210 | 230 | 250 | ||||||||||||
A | B | C | D | E | A | B | C | D | E | A | B | C | D | E | |
GN30-12/400、 630 | 680 |
282 (Parallel on both sides) 363 (Vertical on both sides) |
510 (Parallel on both sides) 575 (vertical on one side) 665 (Vertical on both sides) |
820 |
720 |
282 (Parallel on both sides) 363 (Vertical on both sides) |
510 (Parallel on both sides) 575 (vertical on one side) 665 (Vertical on both sides) |
860 |
760 |
282 (Parallel on both sides) 363 (Vertical on both sides) |
510 (Parallel on both sides) 575 (vertical on one side) 665 (Vertical on both sides) |
900 |
|||
GN30-12/1000 | |||||||||||||||
GN30-12/1250 | |||||||||||||||
GN30-12D/400、 630 | 615 |
615 |
615 |
||||||||||||
GN30-12D/1000 | |||||||||||||||
GN30-12D/1250 |