WhatsApp: +8613967773640 Email: gongshun@electric-cn.com
  

FZN25-12 type vacuum load switch and composite apparatus

Description


Product Description 

FZN25-12D/FZRN25-12D type vacuum load switch and composite apparatus,suitable for three-phase AC 50Hz ring network or terminal power supply and industrial electrical equipment.for load control and short circuit protection use,load switch open and close the closed-loop current,no-load transformer and cable charging current,composite apparatus can break any current till rated short circuit current.Adopt the straight move or isolating fracture and vacuum interrupter linkage.With the function of manual and electric operation.FZRN25 special transmission structure design,arc extinguish chamber only withstand voltage in the moment of closing and breaking,small size,low price.FZN25,FZRN25 can realize isolation fracture and arc extinguish chamber fracture disposable operating FZN25,FZRN25 has a grounding switch mutual linkage grounding valve between the static contact and movable conductive cylinder,ensures safety and convenient maintenance.

Use environment

1.It is suitable for three-phase AC 50/60Hz interruption power supply and industrial electrical equipment
2.For load control and short circuit protection 
3.Load switch breaking load,closed-loop current,no-load transformer and cable charging current
4.The current of the combined apparatus is up to the rated short-circuit current
5.It adopts direct acting isolation fracture and vacuum arc linkage,with manual and electric functions Feature:
6.Unique transmission structure design,small volume and light weight,
7.The interrupter only bears high voltage at the moment of making and breaking.
8.It can realize the one-time operation of isolating fracture and interrupter end fracture
9.There is a grounding valve linked with the grounding switch between the static contact and the moving contact conducting cylinder
10.It is safe and convenient to inspect

Technical parameter
 
No. project units parameter
FZN25-12D/T630-20 FZRN25-12D/T125-31.5
1 Theratedvoltage kV 12
2 Rated frequency HZ 50
3 Rated current A 630 125
4 Ratedinsulationlevel Voltage withstand 1min powerfrequency kV Arcextinguishingchamberfracture30;Totheground,interphase42;Isolationfracture48
Lightning shock withstandvoltage kV To the ground, phase 75; Isolation fracture 85
5 Rated dynamic stability current (peak) kA 50 -
6 4Sheatstabilizedcurrent kA 20 -
7 Rated active load breaking current A 630 125
8 Ratedclosed-loopbreakingcurrent A 630 125
9 Rated cable charging break current A 10 10
10 Turnofftheno-loadtransformercapacity KVA 1250 1250
11 Ratedshortcircuitbreakingcurrent kA - 31.5
12 Rated transfer current, rated transfer current A - 2000
13 Fuse type   - SDLAJ-12SFLAJ-12
14 Impactor outputs energy   - 2-5(medium)
 
Additional Information




 

Get Free Quote Now

Related products